Repository logo
Institutional Digital Repository
Shreenivas Deshpande Library, IIT (BHU), Varanasi

Performance characteristics of low global warming potential R134a alternative refrigerants in ejector-expansion refrigeration system

dc.contributor.authorMishra, Shubham
dc.contributor.authorSarkar, Jahar
dc.date.accessioned2020-02-18T11:10:38Z
dc.date.available2020-02-18T11:10:38Z
dc.date.issued2016-12-01
dc.description.abstractPerformance assessment of ejector-expansion vapor compression refrigeration system with eco-friendly R134a alternative refrigerants (R152a, R1234yf, R600a, R600, R290, R161, R32, and propylene) is presented for air-conditioning application. Ejector has been modeled by considering experimental data based correlations of component efficiencies to take care of all irreversibilities. Ejector area ratio has been optimized based on maximum coefficient of performance (COP) for typical air-conditioner operating temperatures. Selected refrigerants have been compared based on area ratio, pressure lift ratio, entrainment ratio, COP, COP improvement and volumetric cooling capacity. Effects of normal boiling point and critical point on the performances have been studied as well. Using ejector as an expansion device, maximum improvement in COP is noted in R1234yf (10.1%), which reduces the COP deviation with R134a (4.5% less in basic cycle and 2.5% less in ejector cycle). Hence, R1234yf seems to be best alternative for ejector expansion system due to its mild flammability and comparable volumetric capacity and cooling COP. refrigerant R161 is superior to R134a in terms of both COP and volumetric cooling capacity, although may be restricted for low capacity application due to its flammability.en_US
dc.identifier.issn12310956
dc.identifier.urihttps://idr-sdlib.iitbhu.ac.in/handle/123456789/622
dc.language.isoen_USen_US
dc.publisherPolish Academy of Sciencesen_US
dc.subjectArea ratioen_US
dc.subjectCOPen_US
dc.subjectCritical temperatureen_US
dc.subjectEco-friendly refrigeranten_US
dc.subjectOptimizationen_US
dc.subjectTwo-phase ejectoren_US
dc.titlePerformance characteristics of low global warming potential R134a alternative refrigerants in ejector-expansion refrigeration systemen_US
dc.typeArticleen_US

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Performance-characteristics-of-low-global-warming-potential-R134a-alternative-refrigerants-in-ejectorexpansion-refrigeration-system2016Archives-of-ThermodynamicsOpen-Access.pdf
Size:
433.6 KB
Format:
Adobe Portable Document Format
Description:
Open Access Article

License bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description: